manual intervention to restart the pumps for two reasons: | manual intervention to restart the pumps for two reasons: | ||
- | * The operator is responsible for verifying that there is sufficient oil flowing to the pumps before | + | * The operator is responsible for verifying that there is sufficient oil flowing to the pumps before they are allowed to start (" |
- | they are allowed to start (" | + | |
- | the flow indicator near the oil tank and recirculating pump). If there is no, or insufficient, | + | |
- | starting the pumps would likely lead to their self-destruction in short order. | + | |
- | * A power outage that lasts longer than a fraction of a second inevitably leaves the telescope in an | + | * A power outage that lasts longer than a fraction of a second inevitably leaves the telescope in an indeterminate state. It is patently unsafe to resume the delivery of high-pressure hydraulic fluid to the azimuth bearing, and also to hence " |
- | indeterminate state. It is patently unsafe to resume the delivery of high-pressure hydraulic | + | |
- | fluid to the azimuth bearing, and also to hence " | + | |
- | deciding it is safe to do so. | + | |
I don't remember how the original PLC-controlled pump/ | I don't remember how the original PLC-controlled pump/ |