This is an old revision of the document!
Lightning Shutdown & Startup / Jun 6, 2024 / P Gabor | ✔✘ | ||
---|---|---|---|
General Remark | ![]() | ||
General rule 0 | ![]() | ||
General rule 1 | ![]() | ||
Case A | Observatory in “warm” shutdown. | ||
Assumes Don's Automated Shutdown complete ![]() ![]() | |||
Control room | Tom Pack in Remote ; double check that everything is off/inactive/disabled including the Main Don Power | ||
Control room | Tom Pack > Service > General > Power Supply turn all four items off | ||
Control room | Tom Pack > Service > General > Application Exit press EXIT | ||
Control room | In Remote Desktop shut down PC-VATT-1 PC-VATT-2 (You may want to Exit Tom Pack beforehand in both cases) | ||
Control room | Out of the three new X-terms, pick the one where you can reach its own “surfer” desktop most readily (typically by closing various remote sessions). On the X-term's own desktop, open a terminal. In the terminal type either haltvatt or ./haltvatt and hit ENTER . The shutdown script will run, and it will power down every computer, including all four xterms (the three new ones and the older one), the only exception is vatttel . (It is no longer necessary to use the power button on vattdata to shut it down fully). | ||
Note. The haltvatt script is not resident, and so cannot be used, on vattxt3 (the older xterm with the smaller monitor). | |||
Server (Instrument) room | Open the computer rack. Check that the servers are off by inspecting their power indicators (they ought to be amber). | ||
Server (Instrument) room | Press and hold the power button on each of the HP UPSs (bottom of rack, under the vattdata server), until you hear the power go off (~5 sec). | ||
Server (Instrument) room | Close the computer rack. (The doors are electrically bonded to the frames, and a closed rack provides more protection for people and for the computers.) | ||
10kVA UPS room | Press the Power button (top right) until a pop-up screen appears, titled Option with three bullet points: Turn to bypass , Turn off output and Turn off UPS ; select the latter using the arrow keys (bottom center) and press Enter (bottom right) | ||
10kVA UPS room | Another pop-up screen appears, this time asking for confirmation. Confirm by selecting Yes (moving the cursor right) and press Enter (bottom right). | ||
10kVA UPS room | Another pop-up screen appears, titled Notify , advising to Open input breaker to turn off UPS . | ||
10kVA UPS room | Go to Panel C , and open (switch off) the two bound-together circuit breakers marked 10 kVA UPS (top left). | ||
10kVA UPS room | The UPS continues beeping, showing a new pop-up screen, titled Notify , advising that Shutdown in progress . The shutdown concludes in a couple of minutes: the screen goes dark and the beeping stops. | ||
Lvl 1, Telecom room | Go to Panel A , and open (switch off) the three bound-together 100 A circuit breakers marked Panel C (bottom left) in red. | ||
STARTUP | Reverse the steps above | ||
Lvl 1, Telecom room | Go to Panel A , and close (turn on) the three bound-together 100 A circuit breakers marked Panel C (bottom left) in red. | ||
10kVA UPS room | Go to Panel C , and close (turn on) the two bound-together circuit breakers marked 10 kVA UPS (top left). | ||
10kVA UPS room | The UPS starts making noises, showing a pop-up screen, titled Confirm , advising that “New alarm present”, and asking, “Show log?” Select No using the left arrow and Enter . | ||
10kVA UPS room | While the UPS continues to beep, a new pop-up screen appears, titled Confirm , asking, “Turn on UPS?” Select Yes using the right arrow and Enter . The UPS will stop beeping and more subtle noises (clicking) will accompany the startup process. | ||
Server (Instrument) room | Open the computer rack. Press and hold the power button on each of the HP UPSs (bottom of rack, under the vattdata server), until you hear the power go start (~5 sec). | ||
Server (Instrument) room | Turn on the HP servers by pushing their power indicators (they ought to be amber; push them for no longer than 1 sec; they ought to turn green). Other servers have different activation buttons. The two ProjectSoft PC servers have diamond-shaped buttons with a dim white LED. Monitor the process on the KVM as needed. | ||
Control room | Turn on one of the HP Thin Clients. Check that the screen refresh rate is 30Hz (see What's New at VATT > AOC 4k monitors and the HP Thin Client xterminals). Start a remote desktop session on either PC-VATT-1 or PC-VATT-2 (icon on desktop). | ||
Note 1 | Booting up vattdata is slow (approx. 10 mins). You can follow the process on its terminal: On the KVM (keyboard-video-mouse) console (Tips on how to use the unit.), highlight the entry labeled vattdata using the up/down arrow keys, and press Enter . When the RISC drives are mounted and the system is fully booted, the text stops scrolling on the screen and an ASCII list of 12 options appears. This indicates that all is well and no further action is required. | ||
Note 2 | vattdata is no longer a prerequisite for the boot-up of other servers. | ||
Note 3 | Booting up the servers in the computer racks in the Instrument Room. Slide out the KVM (keyboard-video-mouse) console. (Tips on how to use the unit.) Proceed to the other servers and power them all up. You may monitor the progress of this operation using the KVM. If you are still connected to vattdata , hit prn sc and then Alt+D to disconnect from the vattdata text interface. Green or red status indicators appear in the KVM's list of computers. Now you may also connect the KVM to the servers listed (scroll and Enter ). | ||
Note 4 | ![]() Ready and Power ). ![]() VATTtel unless the GPS unit is ready. | ||
Note 5 | Coming out of lightning shutdown the guide box is likely to run into communication problems. The remedy is to run the INDImon script (its launcher on VATTcontrol 's desktop is labeled Restart indidriver ), selecting option (3) Filter/Guidebox driver . See What's New at VATT for more details. |