This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
public:kitt_peak:bok_90:bok_90_inch_lightning_shutdown [2018/08/27 15:40] jeff |
public:kitt_peak:bok_90:bok_90_inch_lightning_shutdown [2019/05/22 13:58] (current) mel |
||
---|---|---|---|
Line 1: | Line 1: | ||
+ | ======Lightning Shutdown, Short Version: Updated 2/ | ||
+ | |||
+ | ===Changes coming out of Downtime 2018=== | ||
+ | - We have an " | ||
+ | - BokCCD2 is now the main Azcam computer for both the B&C and 90Prime instruments. | ||
+ | - There is no longer an UPS under the counter feeding console power. | ||
+ | - The weather computer is now password protected, and the password is posted on the monitor. | ||
+ | |||
+ | |||
===== CASS (B&C, WIFIS, SCC) Lightning Shutdown ===== | ===== CASS (B&C, WIFIS, SCC) Lightning Shutdown ===== | ||
Line 12: | Line 21: | ||
- Turn off IIS readout and unplug | - Turn off IIS readout and unplug | ||
- Turn off IIS motor controller and unplug | - Turn off IIS motor controller and unplug | ||
- | - Turn OFF and unplug ' | + | - Turn off and unplug ' |
- | *Telescope (for other CASS users) | + | *Telescope (for other CASS users [WIFIS, SPOL, SCC, PISCES]) |
- Make sure everything is turned off and unplugged from orange outlets on the bottom of the telescope | - Make sure everything is turned off and unplugged from orange outlets on the bottom of the telescope | ||
- Make sure IIS readout and motor controller are turned off and unplugged. | - Make sure IIS readout and motor controller are turned off and unplugged. | ||
Line 29: | Line 38: | ||
* Unplug dome mic if in use next to AED | * Unplug dome mic if in use next to AED | ||
- Observers Workstation | - Observers Workstation | ||
- | * Shutdown AzCam program, shutdown Azcam computers (BOKCCD2 & BOKCCD4) from start menu, and shutdown AzCam Xterm | + | * Shutdown AzCam program, shutdown Azcam computers (BOKCCD2 & BOKCCD4 |
* Shutdown programs on Bart, shutdown Bart from Start Menu, and Bart Xterm | * Shutdown programs on Bart, shutdown Bart from Start Menu, and Bart Xterm | ||
* Shutdown weather computer | * Shutdown weather computer | ||
-Electronics Computer Rack Area | -Electronics Computer Rack Area | ||
- | * Using the KVM switch make sure all computers in the rack are off (except BOKPOP): | + | * Using the KVM switch make sure all computers in the rack are off (**except BOKPOP**): |
- | * #1 Bokccd2 | + | * #2 Bokccd2 |
- | * #5 Bart (should already be off) | + | * #5 Priscilla |
- | * #6 Priscilla | + | * #6 Bart (should already be off) |
- | * #7 BokPOP (Please leave BOKPOP turned ON) | + | * **#7 BokPOP (Please leave BOKPOP turned ON)** |
- | * Shut down Bokaux computer | + | |
* Turn off flat field lamp controller if in use | * Turn off flat field lamp controller if in use | ||
* Turn off printer | * Turn off printer | ||
* Turn off (3) UPS units in bottom of the rack | * Turn off (3) UPS units in bottom of the rack | ||
- | * Note: The CONSOLE UPS powers the Operators Console, make sure everything in it is turned off first. | + | * Note: The CONSOLE UPS powers the Operators Console, make sure everything in it is turned off first. |
Line 82: | Line 90: | ||
* Shutdown weather computer | * Shutdown weather computer | ||
-Electronics Computer Rack Area | -Electronics Computer Rack Area | ||
- | * Using the KVM switch make sure all computers in the rack are off | + | * Using the KVM switch make sure all computers in the rack are off **except BokPOP** |
- | * #2 Bokccd2 | + | * #2 Bokccd2 |
- | * #4 Bokccd4 | + | * #4 Bokccd4 |
- | * #4 Bart (should already be off) | + | * #5 Priscilla (if in use) |
- | * #7 BokPOP (shoulld | + | * #6 Bart (should already be off) |
- | | + | * #7 BokPOP |
* Turn off flat field lamp controller if in use | * Turn off flat field lamp controller if in use | ||
* Turn off printer | * Turn off printer | ||
* Turn off (3) UPS units in bottom of the rack | * Turn off (3) UPS units in bottom of the rack | ||
- | * * Note: The CONSOLE UPS powers the Operators Console, make sure everything in it is turned off first. | + | * * Note: The CONSOLE UPS powers the Operators Console, make sure everything in it is turned off first. |
*Warm Room Cable Closet | *Warm Room Cable Closet | ||
- Unplug three plugs with red tape on your right as you enter the door down low | - Unplug three plugs with red tape on your right as you enter the door down low | ||
- Unplug 1 twist lock plug with red tape west wall | - Unplug 1 twist lock plug with red tape west wall | ||
- | - Unplug GPS Ethernet cable, BNC cable and power cable on west wall | + | - Plug in Brandywine NTP Server' |
*Second Floor Pier Room | *Second Floor Pier Room | ||
Line 121: | Line 129: | ||
*Electronics Computer Rack Area | *Electronics Computer Rack Area | ||
- | - Turn on (3) UPS units in bottom of the rack | + | - Turn on (3) UPS units in bottom of the rack. On the new Console UPS: You will need to hit the power button, then use the arrow and OK buttons to choose "On Immediately" |
- Turn on Bokpop (it should already be ON) | - Turn on Bokpop (it should already be ON) | ||
- Turn on Bart | - Turn on Bart | ||
- | - Turn on BokAux | + | - Turn on BokAux |
- Turn on printer | - Turn on printer | ||
- **90Prime users** | - **90Prime users** | ||
Line 135: | Line 144: | ||
- Turn on Azcam Xterm, log into BokCCD2 if using B&C or 90Prime. | - Turn on Azcam Xterm, log into BokCCD2 if using B&C or 90Prime. | ||
- Start Bart Xterm, login either as Primefocus Observer if you're using 90Prime, or Bok Observer with any other instrument using appropriate passwords. | - Start Bart Xterm, login either as Primefocus Observer if you're using 90Prime, or Bok Observer with any other instrument using appropriate passwords. | ||
+ | - Start weather computer by pressing button on top of the upper left edge. Enter the password posted on the monitor. | ||
* At the Operators Console: | * At the Operators Console: | ||
- Make sure the CONSOLE UPS is plugged in and turned ON (should be done already if the above steps were followed) | - Make sure the CONSOLE UPS is plugged in and turned ON (should be done already if the above steps were followed) |